THERMODYNAMICS LABORATORY
N3-B2a-01
Lab Sub-Group:
NTU AY06/07 Sem II By Aerospace Engineering Yr 2 Group AE18

Fig 3.1 - Schematic Diagram of Cascade Cycle

F ig 3.2 – T-s Diagram of a Cascade Cycle

Fig 3.3 – Schematic Diagram of an Absorption Refrigeration Cycle
Improvements to the vapor compression refrigeration cycle:
The performance of vapor compression cycle can be improved by the following methods:
-- Cascade Vapor Refrigeration Cycle
-- Multipurpose Compression with intercooling
-- Multistage Compression Refrigeration cycle
-- Gas liquefaction
Cascade Vapor Refrigeration Cycle
Cascade cycles are two or more refrigeration cycle arranged in series. In figure 1 below, the cascade cycle is shown in which two vapor-compression refrigeration cycles, labeled A and B are arranged in series with a counterflow heat exchanger linking them. In the intermedium heat exchanger, the energy rejected during condensation of the refrigerant in the lower temperature cycle A is used to evaporate the refrigerant in the higher-temperature cycle B.
Figure 1: Cascading Cycle
The desired refrigeration effect occurs in the low-temperature evaporator and heat rejection from the overall cycle occurs in the higher temperature condenser. In the cascading cycles, the coefficient of performance is the ratio of the refrigeration effect to the total work input.
A significant feature of the cascade system is that the refrigerants in the two or more stages can be selected to have reasonable evaporator and condenser pressures in the two or more temperature ranges. In double cascade system, a refrigerant would be selected for cycle A which has a saturation pressure-temperature relationship that allows refrigeration at a relatively low temperature without extensively low evaporator pressures. In turn, the refrigerant for cycle B would have saturation characteristics that permit condensation at the required temperature without excessively high condenser pressure.
Multistage Compression with intercooling
Net work output can be increase by decreasing the compressor work consumed. This can be achieved by multistage compression with intercooling the gas between stages. Intercooling is achieved in gas power systems by heat transfer to the lower-temperature surroundings. In refrigeration systems, the refrigerant temperature is below that of the surroundings for much of the cycle. Thus, other means must be employed to accomplish intercooling so as to achieve the attendant savings in the required compressor work input.

Figure 2: Multistage Compression with intercooling

Figure 3: Multipurpose Compression Refrigeration cycle
Gas liquefaction
Refrigeration by liquefaction of gases is the process of refrigerating a gas to a temperature below its critical temperature so that liquid can be formed at some suitable pressure, also below the critical pressure. Gas liquefaction is a special case of gas refrigeration. Firstly, The gas is compressed to a higher pressure in an ambient-temperature compressor. This high-pressure gas is passed through a countercurrent heat exchanger to a throttling valve or expansion engine. Upon expanding to the lower pressure, cooling may take place, and some liquid may be formed. The cool, low-pressure gas returns to the compressor inlet to repeat the cycle. The purpose of the countercurrent heat exchanger is to warm the low-pressure gas prior to recompression, and simultaneously to cool the high-pressure gas to the lowest temperature possible prior to expansion. Both refrigerators and liquefiers operate on this same basic principle.
Figure 4: Gas liquefaction


Figure 2: T-S graph
Figure 3: Excerpt from table 2 – energy balance at compressor
Figure 4: Excerpt from table 2 – energy balance at condenser
Figure 5: Excerpt from table 2 – Coefficients of performance
Firstly, it was observed that COPc is always smaller than COPh. COPc is essentially the measurement of how much heat is extracted in by the refrigerant whereas COPh is the measurement of how much heat is extracted out of the refrigerant.
Secondly, COPc,o and COPh,o are smaller than COPc and COPh. The loss in heat dissipation in converting electrical energy supplied by the compressor motor to the shaft of the compressor explains for the differences
Lastly, the COPs for result 1 is greater than that of result 2. By partially blocking the evaporator outlet, condenser water flow rate was reduced. This means that lesser heat was transferred from the cooler reservoir. Hence, the thermal efficiency of the refrigerator is reduced.

The refrigerant used in the refrigeration unit is R-134a and the condensor coolant used is water. Temperature and pressure at relevant state points in the cycle can be easily read off from a digital temperature reader and the 2 pressure gauges. In addition, refrigerant and condensor coolant flowrates can be obtained directly from flowmeters located on the unit itself. Finally, electrical power input to the motor can be obtained by timing how long the disc of the watt-hour meter take to complete one revolution.


Fig. 2.1 Schematic diagram of refrigerator
A refrigerator is shown schematically in Figure 2.1. Here, QL is the magnitude of the heat removed from the refrigerated space at temperature TL, QH is the magnitude of the heat rejected to the warm space at temperature TH, and Win is the net work input to the refrigerator.
Refrigeration can be classified as:
1. Vapor cycle, and
2. Gas cycle
Vapor cycle refrigeration can further be classified as:
1. Vapor compression refrigeration
2. Gas absorption refrigeration

Fig. 2.2 Ideal vapor compression refrigeration cycle
An ideal vapour compression refrigeration cycle is defined as a refrigeration system that removes thermal energy from a low temperature region and transfers the heat to a high temperature region. The diagram in Figure 2.2 shows the schematic and the T-s graph for an ideal vapor compression refrigeration cycle.
For an ideal vapor compression refrigeration cycle, it consists of 4 main processes:


Figure 2.3 Schematic and T-s diagram for the actual vapor compression refrigeration cycle